2. The magnetic flip level gauge must be installed vertically. The ball valve should be installed between the magnetic flip level gauge and the container lead to facilitate inspection and cleaning.
3. If the user uses the heat tracer, he must use non-magnetic materials such as copper tubes. Heating temperature also depends on the medium conditions to determine;
5, magnetic level gauge before use should be calibrated with magnetic steel ball below the zero position is set to red, other balls set to white;
4. The measured medium should not contain solid impurities or magnetic substances, so as to avoid blocking of the float.
6. Open the bottom flange of the magnetic flip level gauge and install the magnetic float (note that the heavy end is magnetically upward and cannot be flipped).
7, should be based on the measurement of the media, from time to time cleaning the main catheter to remove impurities;
8. For level gauges that exceed a certain length, it is necessary to add intermediate reinforcement flanges or ear climbing as a fixed support to increase strength and overcome its own weight;
9, when the commissioning should first open the upper guide valve, and then slowly open the lower valve, so that the media smoothly into the main catheter (runner medium should avoid rapid impact on the float, causing severe fluctuations in the float, affect the accuracy of the display), Observe that the magnetic red-white ball flips are not normal. Then close the down-lead valve and open the drain valve so that the level in the main duct falls. According to this method three times of operation, it is normal, you can put into operation (except for corrosive and other special liquids);
10. The installation position of the magnetic flip liquid level gauge should be avoided or kept away from the inlet and outlet of the material medium, so as to avoid the accuracy of the liquid level measurement due to the rapid change of the local area of ​​the material fluid.
1. The magnetic plate level gauge should not be surrounded by magnetically permeable materials, nor can it be fixed by wire, because this will affect the normal operation of the magnetic plate level gauge;